F-MPM110 Multifunction Electric Power Meter
Beschreibung
Suit for LV/ HV Voltage System
For low voltage system, direct connect up to 690 v (L-L) AC
For high voltage system, support connect up to 65kV
Ture-RMS Measuring Parameter
True-RMS measuring parameters includes:
U, I, P, Q, S, PF, F, kWh, kvarh, kVAh
Demand Calculation
2 kinds of demand modes: fixed block and rolling block
Power Quality Analysis
31st Harmonic analysis, K factor, unbalance etc.
TOU (Multi-tariff billing), Historical Data of 31 Days and 12 Monate
TOU, 4 tariffs, 8 time period in 24 Std.
Max./ Min. Record (U, I, P, Q*, S*)
Under/ Over Limit Alarm
64M Bit Memory, Build-in Web
Real-time data inquiry by Web
Save monitoring data (Time interval
settable 1min, 5 Mindest, 10Mindest,15Mindest, 30Mindest)
Support FTP for download memory data
CO2 (Carbon Dioxide) Calculation for kWh
Multiple Communication
BACnet MS/TP Protocol (RS485 port)
MODBUS-RTU Protocol (RS485 Port)
MODBUS-TCP/IP Protocol (Ethernet port )
DI / DO
High Accuracy
Active energy: according to IEC62053-22, class 0.5s
Reactive energy: according to IEC62053-23, class 2
Basic Function | |||
Real time metering | Stromspannung | Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg | |
Aktuell | Ia, Ib, Ic, Im, Iavg | ||
Leistung | Pa, Pb, Pc, ∑P, Qa, Qb, Qc, ∑Q, Sa, Sb,Sc, ∑S | ||
Power Factor | PFa, PFb, PFc, ∑PF | ||
Energie | kWh, kvarh, kVAh * | ||
CO2 (Carbon dioxide) | |||
Frequenz | F | ||
Demand & max. Demand | Dmd_I, Dmd_P, Dmd_Q ,Dmd_S | ||
Max./ Min. Value | Max./ min. (U, I, P, Q*, S*) | ||
Multi-tariff Energy * | |||
Phase Angle * | |||
Power Quality Analysis | Unbalance | U_unbl *, I_unbl * | |
Harmonic (31st ) | THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi, HRU *, RHI * | ||
Harmonic RMS (0-31st ) | Harmonic RMS-U *, Harmonic RMS-I *, Harmonic RMS-P * | ||
Harmonic energy (1st -13th ) | |||
Voltage crest factor, current K factor, Load rate, Voltage deviation, Frequency deviation Running time record for power-on period and qualified voltage & current * | |||
Setpoint Alarm | Over/ under limit alarm | ||
3DI +2 DO | 3 status input + 2 relay output | ||
RS485 | Modbus-RTU protocol | ||
Record Function | SOE (event log), Real-time clock ( yyyy-mm-dd hh:mm:ss) * | ||
Voltage/ frequency deviation, Voltage unbalance record |
Optional Module | |||
SW | 4 status input (wet contact) | LAN | 64M bit memory + Ethernet TCP/IP |
SD | 4 status input (dry contact) | KI | 2 analog input (4-20mA) |
C * | The 2nd RS485 | AO | 2 analog output (4-20mA) |
Ep * | 2 pulse output | BA | BACnet MS/TP protocol |
R | 2 relay output | ||
* means some of function can’t be read through BACnet communication port |
Parameter | Genauigkeit | Auflösung | Messbereich |
Stromspannung | 0.2% | 0.01v | Direct: 690Vph-ph |
PT primary: 0.001kV~65kV (settable) PT secondary: 1~398V (settable) | |||
Aktuell | 0.2% | 0.001EIN | CT primary: 1~9,999A (settable) CT secondary: 1 A or 5A |
Leistung | 0.5% | 0.1W/var/ VA | each phase: 0~649.9MW/ Mvar/ MVA |
Gesamt: 0~1949.8MW/ Mvar/ MVA | |||
Power Factor | 0.5% | 0.001 | -1.000~+1.000 |
Frequenz | 0.01 | 0.01Hertz | 45~ 65 Hertz |
Active Energy | 0.5% | 0.1kWh | 0~ 99,999,999.9 kWh |
Reactive Energy | 2.0% | 0.1kvarh | 0~ 99,999,999.9 kvarh |
Apparent Energy | 1.0% | 0.1kVAh | 0~ 99,999,999.9 kVAh |
THD | 1.0% | 0.001 | 0~100.0% |
Individual Harmonic | 1.0% | 0.001 | 0~100.0% |
Un-balance | 1.0% | 0.001 | 0~100.0% |
Connection mode | 3-phase 3-wire, 3-phase 4-wire, 1-phase 2-wire | Communicati-on | Modbus-RTU Protocol | RS485 serial Baud rate: 2400, 4800, 9600, 19200, 38400bps Adresse: 1~247 |
Messung | True RMS, 1 sec refresh time | |||
Eingang | Rate current: 1A or 5A Rate voltage: Direct 120, 220v, 240v, 277v, 398Vph-N (Optional) PT secondary: 1~398V (settable) Frequenz: 50/ 60Hertz | Modbus-TCP/ IP | Ethernet communication port Support connect 10M/100M ethernet, Modbus TCP/IP, Web, FTP | |
Überlast | 120% of rated, continuously Instantaneous current: 10 times/ sec Instantaneous voltage: 2 times/ sec | BACnet MS/TP protocol | RS485 serial Baud rate: 2400, 4800, 9600, 19200, 38400, 57600, 76800bps Adresse: 1…127, excluding 99 | |
Status input | Wet contact, external power supply | |||
Relay output | Node capacity: 250VAC/5A | Abmessungen (L x W x H) | F-MPM110: Panel: 96 x 96 x 13.5 mm Cut-out: 90 x 90 x 58.6 mm (basic) 90 x 90 x 80.1 mm (optional module) F-MPM110-DR: Panel: 96 x 96 x 12 mm Cut-out: 90 x 90 x 58.6 mm (basic) | |
Pulse output | Pulse constant: 1000~9999 programmable Pulse width: 60~100ms programmable Formula: 1 pulse = (1÷ pulse constant ×PT ×CT) kWh | |||
Stromversorgung | 85 ~265VAC,85~265VDC (When select P1) 100~420VAC, 100~400VDC (When select P2) | |||
Power loss | <5VA | Gewicht | Basic unit: approx 550gr. Optional module: 50gr. | |
IP index | IP52 (front panel) and IP30 (Fall) | Umfeld | Main Module & and other Modules | Betriebstemperatur: -10℃~ +55 ℃ Lagertemperatur: -40℃~ +70 ℃ Feuchtigkeit: 5%~95% non-condensing |
Power frequency withstand voltage | AC 2KV/minute | |||
Insulation resistance | ≥50MΩ | BACnet Module | Betriebstemperatur: 0℃~ +50 ℃ Lagertemperatur: -5℃~ +75 ℃ Feuchtigkeit: 10%~95% non-condensing | |
Impulse withstand voltage | 4kV (peak), 1.2/50uS |
Standard(EMV) | |||
Electrostatic discharge immunity test | IEC 61000-4-2,Level 4 | Surge immunity test (1, 2/50μs~8/20μs) | IEC 61000-4-5,Level 3 |
Radiated immunity test | IEC 61000-4-3,Level 3 | Conducted emissions | EN 55022,Class B |
Electrical fast transient /burst immunity test | IEC 61000-4-4,Level 4 | Radiated emissions | EN 55022,Class B |
F-DEM130 DIN Rail Energy Meter
F-MPM100 Multifunction Meter
F-PQA100 Power Quality Analysis
Zusätzliche Information
Herkunftsort: | Fujian, China |
---|---|
Markenname: | Four-Faith |
Modellnummer: | F-MPM110 |
Measuring Current Range: | 0~999999.9A |
Measuring Voltage Range: | 0~999999.9 |
Genauigkeitsklasse: | Class 0.5 |
Betriebstemperatur: | -10℃~ +55 ℃ |
Maße: | 96 x 96 x 12 mm |
Connection Mode: | 3 phase 3 wires, 3 phase 4 wires |
Messung: | True RMS, 1 sec refresh time |
Eingang: | Nennstrom: 5A or 1A Rated voltage: 220/380v, 35Hz~65Hz |
Stromversorgung: | AC 85~265V or DC 100~300V |
Power loss: | <5VA |
IP index: | IP54 (front panel) and IP20 (Fall) |
Gewicht: | Ca. 500gr. |
Name: | F-MPM110 Multifunction Electric Power Meter |