Vendita!

Outdoor 11lkv 12KV 24lv 33kv High Voltage auto Circuit Recloser

Categoria:

Descrizione

Outdoor 11lkv 12KV 24lv 33kv High Voltage auto Circuit Recloser

Descrizione del prodotto
Specifica
Summary
Four-faith Smart Power strives to bring our customers the latest technology and competitive pricing and best service for distribut
ion automatic.
The F-OCB series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applicati
ons for all voltage classes 11kV up to 38kV at 50/60Hz power system. and it’s rated current can reach 1250A.
The F-OCB series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault de
tection, on-line monitoring of closing or opening.

Service environment
1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
2.Umidità: Monthly average humidity 95%; Daily average humidity 90% .
3.Altitude above sea level: Maximum installation altitude: 2500m or more higher.
4.Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
5.Summer barometric 84.7Kpa(635mmHg) Winter barometric 85.6Kpa(642mmHg) Max wind speed 34m/s
6.Humidity of 13mg and Vapour Pressure 17mm/Hg. No frequent violent shake.


Offering
With optional classes for installation styles:
Monofase, vacuum recloser and Three phase, vacuum recloser. With optional relay protection curves for user choice: Instantaneo
us over-current protection.
Timing over-current protection.
Negative sequence over-current protection. Directional over-current protection(*).
Over-voltage protection./Under voltage protection. More relay functions can be customized.
With optional choice by locally or remotely.
With optional communication protocols & I/O port for user choice: RS-232 and RS-485 ports supporting.
DNP3.0 communication protocol support(*). Modbus communication protocol is optional(*). CEI 60870-5-101 communication protocol
supporto.
CEI 60870-5-104 communication protocol support.(*).
The recloser can communicate through GPRS(Or GSM) modem with English or Chinese language (*). With optional functions for user.
Rated currents, System phase current.
Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequenza, energia(kWh), reactive power(kV arh),
power factor .
With optional reclosing interval for user pre-program: Reclosing times setting support.
Dead time setting support.

With events recording function: SOE 1000 operations record.
Fault record and normal operation record.
Nota: (*) mean should customized by manufacturer if needed.

Elemento
Unit
Dati
Tensione nominale
kV
11/15
27
38
Corrente nominale
UN
400/630/800/1250
Frequenza nominale
Hz
50/60
Rated short circuit breaking current
kA
12.5/16/20/25
Rated short current switching current(peak)
kA
31.5/40/50/63
Lightning impulse withstand voltage(peak)
kV
95/110
125/165
170/200
Rated peak value withstand current
kA
31.5/40/50/63
4S short time withstand current
kA
12.5/16/20/25
Rated operating circulate
O-0.5S-CO-2S-CO-5S-CO
Breaking current frequency under rated short circuit
time
200
Mechanism life
time
30000
Secondary loop 1 min power frequency withstand
kV
2

Informazioni aggiuntive

Luogo d'origine:

Fujian, Cina

Marchio:

Four-Faith

Numero di modello:

F-FTU200

Nome del prodotto:

auto recloser

Air temperature:

-45℃-+85℃

Umidità:

Monthly average humidity 95%; Daily average humidity 90%

Altitude above sea level:

2500m or more higher

barometric:

Summer barometric 84.7Kpa(635mmHg) Winter barometric 85.6Kpa(642mmHg)

Corrente nominale:

400/630/800/1250 UN

Frequenza nominale:

50/60 Hz

Rated operating circulate:

O-0.5S-CO-2S-CO-5S-CO

Mechanism life:

200 time