Ultrasonic heat meter(DN15-DN50)

Descrição

Ultrasonic heat meter(DN15-DN50)

1) Water will release heat if temperature decreases. Released heat is ratable with temperature difference and flowing volume through meter.

2) Flowing volume signal comes from flow sensor, temperature difference comes from temperature sensor pair,as result the calculator will calculate heat according to the flowing volume and temperature difference.

3) Measurement unit: Kwh, Gcal for option

4) For Ultrasonic heat meter, communication via M-BUS, RS-485 for option.

Models and Specifications

ModeloQn(m3/h)Comprimento(milímetros)DN(milímetros)Sensor lengthDisplayRomoteAula
RLM(C)-15-0.60.6110151.5mkw/hM-BUS2
RLM(C)-15-1.51.5110151.5mkw/hM-BUS2
RLM(C)-20-2.52.5130201.5mkw/hM-BUS2
RLM(C)-25-3.53.5160251.5mkw/hM-BUS2
RLM(C)-32-6.06180321.5mkw/hM-BUS2
RLM(C)-40-1010200401.5mkw/hM-BUS2

Características:

1.Flow range:0.03~20m3/h
2.Minimum temperature difference is 3℃
3.Can be mounted in both horizontal and vertical running pipes
4.Intelligent design and can record energy and flowing volume.
5.Tamanho pequeno, Light weight and beautiful appearance.
6.Measuring device have no motion parts and no abrasion.It won’t be affected by working time.
7.High accuracy and meet EN 1434 metrological class B and CJ128 metrological class 2.
8.Mais do que 10 year long-life battery
9.M-BUS, RS-485 remote system.
10.Not affected by external magnet field and steady
11.function.Electronic parts can be took down from flow sensor and
12.easy reading.
13.Total flow range(q s/q i =100:1)
14.Low start flow volume
15.Can calculate both heat and cold energy.Installation in the return flow line(optionally in
16.forward flow line)
17.Temperature sensor pair Pt1000.
18. Environment temperature grade:UMA

Main Technical Parameters:

Normal Flow(Qn)0.6m3/h1.5m3/h2.5m3/h
Flow range(m3/h)0.012~1.20.03~30.05~5
Pressure loss(KPa/Qp)
Reference diagram I
242424
Máx.. Pressure(MPa)1.6
Temperature range(℃)4~95

Pressure Loss Diagram:

Measuring Features:

Water will release heat if temperature decreases. Released heat is ratable with temperature difference and flow volume through meter. Flow volume signal comes from flow sensor, temerature difference comes from temperature sensor pair, as result the calculator will calculate heat according to the flowing volume and temperature difference.

Water pressure: ≤1.6Mpa
Measuring accuracy: Aula 2
The max tolerance is shown in the curve below:
E=±(3+4Δθmin/Δθ+0.02qp/q)%
Therein,Δθmin means the minimum temperature difference, and Δθthe actual temperature difference.

Dimensional Parameters:

Normal flow(Qn)m3/h0.61.52.53.5
Normal DNmilímetros15152025
Body thread—-G3/4”BG3/4”BG1”BG1 1/4”B
Connection thread—-1/21/23/41″
Alturamilímetros115115105110
Comprimentomilímetros110110130160

Temperature sensor pair

Temperature sensor pair PT1000 meets Norm. DIN EN60751

Sensor is soldered on PCA. The length of sensor lead is 1.5m. (Optional 3m, 10m)

Diameter of sensor is diameter 5.0mm(optional diameter 5.2mm )

Mounting for heat meters:

Heat system pipeline

If you are interested in our water meter or have any questions, por favor sinta-se livre para entrar em contato conosco!

Informação adicional

Lugar de origem:

China

Marca:

ZETON

Número do modelo:

RLM(C)-15

Display Type:

Digital Only

Estágio:

Nenhum

Measuring Energy Range:

Nenhum

Accuracy Class:

Aula 2

Voltagem de saída:

Nenhum

Temperatura de operação:

0-95 grau

Dimensões:

DN15mm ,DN20mm,DN25mm

Material of body:

Brass

Label on head:

In English or Russia

Measure unit:

Kwh, Gcal for choice

Voltage for M-BUS:

3.6V

Voltage for RS-485:

15V to 24V for Russia

Remote communication:

M-BUS, RS-485, Infrared port

Inner box:

Yellow box, suits special design

Outer box:

Yellow box, suits special design

DN15mm Flow rate:

Qn = 0.6m3/h. Qmax= 1.2m3/h,Qmin= 0.012m3/h